VELOX SAFE-T, SELF-LIMITING CABLE
 |
- Sheath of Teflon (CT)
- Armouring 1.5mm²
- Armouring layer of thermoplastic rubber (CR)
- Semiconductive material with self-limiting characteristics (the resistance inreases with rising temperature)
- Conductor
|
Area of use
Roof applications.
Cble data
| Basic type |
65 CM acc.to SS 424 24 11 |
| Tested and approved by |
SEMKO (Sweden) • SETI (Finnland) • UL (USA) • Det norske Veritas • Bureau Veritas |
| Rated voltage: |
220 – 240 V |
| Output W/m |
-10°C in air ≈ 22 W/m
0°C in air ≈ 19 W/m
+65°C in air ≈ 2 W/m
0°C in ice/water ≈ 36 W/m |
| Maximum cable length for max. 20% power loss |
58 meter |
| Installation temperature |
min -20°C |
| Bending radius |
min 25 mm |
| Dimension: |
11.1 x 5.0 mm |
| Weight: |
118 kg/1000m |
| Part.no |
89 861 45 |
Max. cable length based on fuse and start-up temperature. Supply voltage 230/240V
Table 1
| Fusing |
Cable length/Start-up temperature |
| -20°C |
0°C |
+10°C |
| 10 A |
30 m |
40 m |
50 m |
| 16 A |
48 m |
64 m |
78 m |
| 20 A |
60 m |
80 m |
97 m |