VELOX BTL-10, SELF-LIMITING CABLE
 |
- Sheath thermoplastic rubber (CR) or Teflon (CT)
- Armouring Cu
- Armouring layer of thermoplastic rubber (CR)
- Semiconductive material with self-limiting characteristics (the resistansce increases with rising temperature)
- Conductors Cu 1.3mm² (16 AWG)
|
Area of use
Frost protection of piping, tanks.
Cable data
Basic type |
65 CM acc. to SS 424 24 11 |
Tested and approved by |
SEMKO (Sweden) • SETI (Finnland) • UL (USA) • Det norske Veritas • Bureau Veritas |
Rated voltage: |
220 – 240 V |
Output W/m |
0°C – 12 W/m
+10°C – 10 W/m
+65°C – 2 W/m |
Maximum cable length for max. 20% power loss |
97 meter |
Installation temperature |
min -20°C |
Bending radius |
min 25 mm |
Dimension |
7.5 x 5.0 mm |
Weight: |
65 kg/1000m |
Part.no |
89 861 30 |
Max. cable length based on fuse and start-up temperature. Supply voltage 230/240V
Table 1
Fusing |
Cable length/Start-up temperature |
-30°C |
0°C |
+10°C |
10 A |
70 m |
110 m |
135 m |
16 A |
105 m |
175 m |
195 m |
Max. length per loop depending on voltage drop in the conductors.
Max. length per installed length:
100 m at external applications
60 m at internal applications in water pipes