VELOX BTL FLOORHEAT, SELF-LIMITING CABLE
 |
- Sheath of TPE
- Armouring 1.5mm²
- Armouring layer
- Semiconductive material with self-limiting characteristics (the resistance increases with rising temperature)
- Conductor
|
Area of use
Floor heating.
Cable data
Basic type |
65 CM acc. to SS 424 24 11 |
Tested and approved by |
SEMKO (Sweden) • SETI (Finnland) • UL (USA) • Det norske Veritas • Bureau Veritas |
Rated voltage: |
220 – 240 V |
Output W/m |
+20°C ≈ 18-20 W/m |
Max. cable length for max 20% power loss |
62 meter |
Installation temperature |
min -15°C |
Bending radius |
min 25 mm |
Dimension: |
7.5 x 5.0 mm |
Weight: |
65 kg/1000m |
Part.no |
89 861 50 |
Max. cable length based on fuse and start-up temperature. Supply voltage 230/240V
Table 1
Fusing |
Cable length/Start-up temperature |
-20°C |
0°C |
+10°C |
+20°C |
10 A |
37 m |
44 m |
72 m |
79 m |
16 A |
60 m |
77 m |
127 m |
140 m |