FUNCTIONS
- Switching and isolation function controlling
- Protection against the effects of sinusoidal alternating earth fault currents
- Protection against indirekt contacts and additional protection against direct contacts.
- Protection against fire hazard caused by insulation faults.
- Used inresidential building, non-residential building, energy sources, industry and infrastructure.
FEATURES
- Electromagnetic type, voltage independent.
- The handle being sealable or equipped with padlock bracket avoids dangerous operationg changes (ON / OFF)
– The handle provides a clear indication of the contact position
– Adequate printing of all data on the front provides long-term identification
TECHNICAL DATA
| Standards: | IEC 61008-1 |
| Approvals | CE, SEMKO, CB |
| Type (wave form of the earth leakage sensed): | AC.A |
| Trip time type: | General use, Selectivity of S |
| Number of poles: | 2, 4 |
| Rated current in (A): | 16, 25, 40, 63 |
| Rated voltage Ue (VAC): | 230/400 |
| Rated frequency Fn (Hz): | 50/60 |
| Rated residual currents (IDn(mA): | 10(2P 16A), 30, 100, 300 |
| Rated conditional short-circuit current: | Inc=iDc=6000A SCPD säkering 100A Gg |
| Making and breaking capacity lm (A): | 1,000 |
| Rated residual breaking capacity (IDm (A): | 1,000 |
| Rated impulse withstand voltage (1.2/50) Uimp (kV): | 8 |
| Dielectric test voltage at ind. freq. for 1 min. (kV): | 2.5 |
| Electrical life (times): | 10,000 |
| Mechanical life (times): | 20,000 |
| Degree of protection: | IP20, with connected conductors |
| Mounting position: | Any |
| Conductor cross-sections Solid and stranded: Finely stranded with end sleeve (mm²): |
0.75-16 0.75-10 |
| Terminals tightening torque (N m): | 2.5-4 |
| Ambient temperature (°C): | -25 ~ +45, max 95% humidity |
| Storage temperature (°C): | -40 ~ +75 |
| Altitude (max (meters)): | 2,000 |