Dimensioning

TANKS ABOVE GROUND

Required power:

The total power required is calculated as per below:

Pt = A x k x dt x 1.25 x S / I

Pt = The required power (Total power in W).
A = The heatable sheath surface in m²
k = The heat permeability of the insulation in W/m°C
(for mineral wool = 0.046)
dt = The difference in temperature in °C
(the lowest permitted temperature of the medium minus the lowest frequent ambient temperature)
S = Safety factor, is put to 1.3-1.7 depending on how it is exposed to weather and wind.
I = The thickness of the insulation in meter.