BTL-Floorheat

VELOX BTL FLOORHEAT, SELF-LIMITING CABLE
btl10-nummer
  1. Sheath of TPE
  2. Armouring 1.5mm²
  3. Armouring layer
  4. Semiconductive material with self-limiting characteristics (the resistance increases with rising temperature)
  5. Conductor

Area of use

Floor heating.

Cable data

Basic type 65 CM acc. to SS 424 24 11
Tested and approved by SEMKO (Sweden) • SETI (Finnland) • UL (USA) • Det norske Veritas • Bureau Veritas
Rated voltage: 220 – 240 V
Output W/m +20°C ≈ 18-20 W/m
Max. cable length for max 20% power loss 62 meter
Installation temperature min -15°C
Bending radius min 25 mm
Dimension: 7.5 x 5.0 mm
Weight: 65 kg/1000m
Part.no 89 861 50

Max. cable length based on fuse and start-up temperature. Supply voltage 230/240V

Table 1

Fusing Cable length/Start-up temperature
-20°C 0°C +10°C +20°C
10 A 37 m 44 m 72 m 79 m
16 A 60 m 77 m 127 m 140 m